Lesson Meters and conductors · Conductor sizing
Conductor voltage drop
Voltage drop (VD) is the loss of voltage along a conductor because of its resistance. Long runs, high current, and small wire increase drop. Motors and compressors need stable voltage at the load—not just at the panel. Use the field formula VD = 2 × K × I × L / CM for single-phase copper (round-trip length), compare to 3%/5% guidelines, and upsize wire when the far end sags too much under load.
Why voltage drop is a field problem
Wire has resistance. Current through that resistance creates a voltage loss according to Ohm's law. The load receives source voltage minus drop.
Symptoms at the load end:
- motors hard starting, overheating, shortened life,
- dim lighting, flicker when loads kick in,
- controls dropping out when a compressor starts,
- inconsistent heater output.
A circuit can be code-legal on ampacity and still fail in operation because drop is too high. Always check drop on long feeders and critical motor circuits.
Single-phase voltage drop formula
For single-phase, two-wire (hot and neutral return), copper conductors, the common field formula is:
`` VD = (2 × K × I × L) / CM ``
Where:
| Symbol | Meaning |
|---|---|
| VD | Voltage drop (volts) |
| 2 | Out and back—round-trip length of one conductor path |
| K | Resistivity constant — 12.9 for copper at 75°C (use 21.2 for aluminum in parallel formula practice) |
| I | Load current (amperes) |
| L | One-way length in feet (panel to load) |
| CM | Conductor area in circular mils (from AWG table) |
Percent drop:
`` %VD = (VD / source voltage) × 100 ``
Example: 240 V circuit, VD = 7.2 V → 3% exactly.
Use line-to-neutral voltage for 120 V branch calculations and line-to-line for 240 V single-phase loads—stay consistent with how you report percent.
Three-phase note
Three-phase feeders use a different multiplier (often √3 and 1.732 forms) because geometry differs. Delmar and NEC examples cover three-phase separately. On the job, use a listed calculator or NEC information annex for three-phase VD when you are not doing single-phase homeruns.
This lesson focuses on the single-phase 2×K×I×L/CM pattern most helpers use first for branch and small feeder checks.
K factor and material
K bundles resistivity and unit conversions for quick field math.
- Copper: K ≈ 12.9
- Aluminum: K ≈ 21.2 (higher drop per CM—expect larger Al wire for same VD)
CM comes from NEC Chapter 9 or wire tables (#12 ≈ 6530 CM, #10 ≈ 10380 CM, #6 ≈ 26240 CM—verify exact values in current tables).
NEC recommendations: 3% and 5%
NEC Informational Notes (not always enforceable as code unless adopted locally) suggest:
- 3% maximum voltage drop on branch circuits (feeder + branch combined often targeted 5% total from service to final outlet).
Many jurisdictions treat these as design standards. Even where not law, they are excellent engineering targets:
| Segment | Typical design goal |
|---|---|
| Branch circuit alone | ≤ 3% |
| Feeder + branch combined | ≤ 5% |
Motor circuits especially suffer when drop exceeds ~3% at running voltage—starting current magnifies the problem.
Load current for VD calculation
Use actual or design load current, not breaker rating:
- Continuous load → full calculated amps,
- Motor → use FLA or 125% where design rules require for sizing context,
- Receptacle general loads → calculated load per NEC demand rules, not 20 A because breaker is 20 A.
Calculating VD at breaker maximum while load is small gives false comfort. Calculate at expected operating amps.
When to upsize wire
If calculated %VD exceeds your target:
- Increase AWG (lower gauge number → larger CM),
- Reduce length (relocate panel—often not optional),
- Raise source voltage (240 V instead of 120 V for same power where equipment allows),
- Parallel conductors per NEC rules (next lesson) to increase effective CM.
Upsizing one step (e.g., 12 → 10 AWG) often fixes marginal residential runs. Long commercial feeders may jump several sizes or use parallel sets.
Measuring drop in the field
With equipment running:
- Measure voltage at source (panel or disconnect).
- Measure voltage at load terminals under same load.
- Difference ≈ actual drop (includes connections—corrosion shows up here).
Compare to calculated prediction. Large gap suggests bad connection, not just wire length.
Static no-load voltage checks miss drop under current—always test under load when possible and safe.
Field case
Situation. A barn 180 feet from the house has a 120 V, 20 A circuit on 12 AWG. Lights OK idle; air compressor hums and trips on start. No-load at barn: 118 V. Under start: 102 V.
What happened. Drop under inrush is severe. Calculated running drop might pass; motor start pulls multiples of FLA. Undersized feeder length for 12 AWG at that distance.
Applied lesson. Run VD at starting and running current; upsize to 10 AWG or 8 AWG, or install 240 V circuit with step-down at barn if load allows. Measure under load to verify fix.
In the field
Symptom
Motors fail to start, dim lights, low voltage only when load runs
Where to look
Long homeruns, temporary extension cords, undersized subfeeders
Likely causes
- Excessive VD
- high-resistance connections
- wrong K or CM in calc
What to measure
- Source vs load voltage **under load**
- actual amps with clamp
What not to do
- Accept no-load voltage as proof
- size wire from breaker amp only
Checklist
- I use **VD = 2 × K × I × L / CM** for single-phase copper checks
- I use **K = 12.9** (Cu) or **21.2** (Al) consistently with material
- I target **3% branch / 5% total** as design guidance
- I calculate with **load current**, not breaker rating
- I verify with **loaded** voltage measurements when safe
- I upsize wire or reconfigure when calculated drop exceeds limits